PC705 Variable Speed Pump Mixing Control
Performance Data
MIX Start: 35 to 150°F (2 to 66°C)
Factory: 70°F (21°C)
Factory: 70°F (21°C)
OUTDR Start: 35 to 85°F (2 to 29°C)
Factory: 70°F (21°C)
MIX DSGN: 70 to 220°F (21 to 104°C)
Factory: 120°F (49°C)
OUTDR DSGN: -60 to 32°F (-51 to 0°C)
Factory: 10°F (-12°C)
MIX MAX: 80 to 225°F (27 to 107°C)
Factory: 180°F (82°C)
BOIL MIN: OFF, 80 to 180°F (OFF, 27 to 82°C)
Factory: 140°F (60°C)
WWSD: 35 to 100°F, OFF (2 to 38°C, OFF)
Factory: 70°F (21°C)
Unit: °F, °C
Factory: °F
Features
- Ambient conditions: Indoor use only, 32 to 104°F (0 to 40°C), < 90% RH non-condensing.
- Power supply: 24 V (ac) ±10% 50/60 Hz 3 VA
- Variable Pump: 120 V 50/60 Hz 2.4 A 1/6 hp
- Pump Relay: 120 V (ac) 5 A , 1/3 hp, pilot duty 240 VA
- Boiler Relay: 24 V (ac) 5 A 1/6 hp, pilot duty 240 VA
Sensors Included:
- NTC thermistor, 10 kW @77°F (25°C ±0.2°C) ß=3892
- Outdoor Sensor M 2036 and 2 of Universal Sensor 071
Applications
- Hot Water Heating Systems
- Closed Cooling Circuits
- Air Conditioning Systems
- Hydronic Heating & Cooling
- Water/Glycol concentrations up to 50%
- Solar / Geothermal