iSeries Mixing Valves
Performance Data
Max. Operating Pressure: 300 psi, (2,100 kPa)
Fluid Temp. Range: 20°F to 240°F (-7°C to 115°C) @ 135°F (57°C) ambient
Ambient Conditions: Indoor Use Only, -22°F to 185°F (-30°C to 85°C), < 90% Non-Condensing Service: Closed Systems, Hot and Chilled Water, up to 50% Glycol
Seat Leakage: Drop-Tight Close Off
Power Supply: 24 VAC ±10% 50/60 HZ
Electrical Rating: 24 VAC, 60 HZ, 0.4 Amps. Do not exceed number of valves per transformer rating. Example: Do not use more than 4 valves per 40VA transformer
Sensors: NTC Thermistor, 10 k Ω @ 77°F (25°C ±0.2°C) β=3892
Features
- 2-way Injection, 3-way or 4-way Mixing
- Operates Off Constant Power or Relay End Switch
- Ball Valve Design, High Cv
- Manual Operation Button
- Solid State Microprocessor Design
- Compact Design
- Easy, One-handed Actuator Removal
- 125 PSI Shutoff Pressure
- Plug-in Low Voltage Connections
- Multi-Status LED Indicator Light
- Fail Safe Mode
- Sensors Included
Applications
- Hot Water Heating Systems
- Closed Cooling Circuits
- Air Conditioning Systems
- Hydronic Heating & Cooling
- Water/Glycol concentrations up to 50%
- Solar / Geothermal