3450 Combination Boiler Feed & Backflow Valve
Performance Data
Max. Inlet Pressure: 150 psi (10.3 Bar)
Min. Delta P Inlet to Outlet: 15 psi (1 Bar)
Recommended Setting Range: 10-50 psi , +/-3 psi , (.7-3.4 bar)
Factory Setting: 12psi (.8)
Adjustment Capability: 8.5 – 65 psi, (.6-4.5 bar)
Max. Flow Rate: 25 gpm (8 ft / sec), 95 l/m
Max. Temp.: 210˚F (99˚C)
Features
- Auto Reset from Fast Fill
- ASSE 1081-2014
- Simple Pressure Adjustment
- Serviceable Cartridge for both the Backflow and Feed Valve
- Adjustable 360 View of Pressure Indicator
- Large Adjustment Range
- Serviceable without draining the system
- One Piece Body Construction
- Stainless Steel Strainer
Applications
- Hydronic Heating Systems